@inproceedings{abf085eb7012483d86a82812c859904d,
title = "Air infiltration caused by wind and stack effect in ice rink",
abstract = "Outdoor moisture infiltration into an ice rink in Taipei was investigated with experimental measurements of temperature, humidity, and pressure difference. Altogether four difference operating indoor conditions and also four points on IIHF fog lines were studied. Year round analysis showed that stack effect and wind effect are important factors of infiltration rate. Seasonal indoor and outdoor temperature difference could result in 2.58 times difference of air infiltration rate, and air change as high as 0.64 ach.",
keywords = "Energy saving, Heat load, Ice rink, Infiltration, Stack effect, Wind effect",
author = "Lin, {Jin Taung} and Chuah, {Yew Khoy}",
year = "2009",
language = "英语",
isbn = "9868509610",
series = "4th Asian Conference on Refrigeration and Air-Conditioning, ACRA 2009",
publisher = "National Taipei University of Technology",
pages = "88--95",
booktitle = "4th Asian Conference on Refrigeration and Air-Conditioning, ACRA 2009",
note = "4th Asian Conference on Refrigeration and Air-Conditioning, ACRA 2009 ; Conference date: 20-05-2009 Through 22-05-2009",
}