An experimental study of falling film evaporation on horizontal tubes using R-134a

L. H. Chien*, R. H. Chen

*此作品的通信作者

研究成果: 期刊稿件文章同行評審

29 引文 斯高帕斯(Scopus)

摘要

This study investigates evaporation heat transfer performance of refrigerant R-134a falling film on three horizontal copper tubes in a vertical column. Experiments were performed at saturation temperatures of 10 and 26.7C. The liquid flows through a liquid feeder with a row of circular holes at a rate of 0.0075 0.0363kg/ms, while heat fluxes varied from 4.5 to 48.5kW/m 2. A smooth tube, a fin tube of 0.4mm fin height, 60FPI (Fins Per Inch), and a new boiling enhanced tube (mesh tube) were tested. The test results show that heat transfer coefficient of the smooth tube increases with increasing heat flux and fluid temperature, and increases slightly with increasing flow rate before dry-out occurs. At low flow rates (less than 0.015kg/ms) or when Ref (255), the fin tube is in thin film evaporation mode and results in a large heat transfer coefficient. At high flow rates (0.0225, 0.03, and 0.0375kg/ms) the falling film evaporation curves are similar to those in pool boiling. For all tubes, the fluid temperature and the flow rate have only minor influences on heat transfer coefficient before dry-out occurs. The 60 FPI tube and the mesh tube enhance the falling film evaporation heat transfer coefficient 6.3 8.29 fold and 1.9 5.0 fold, respectively, as compared with the smooth tube. A new correlation of falling film evaporation, accounting for contributions of nucleate boiling and spray convection, is proposed. It predicts h-values of the falling film evaporation data of the smooth surface within 30%.

原文英語
頁(從 - 到)319-327
頁數9
期刊Journal of Mechanics
28
發行號2
DOIs
出版狀態已出版 - 06 2012
對外發佈

指紋

深入研究「An experimental study of falling film evaporation on horizontal tubes using R-134a」主題。共同形成了獨特的指紋。

引用此