跳至主導覽 跳至搜尋 跳過主要內容

Exergy and thermoeconomic analysis for an underground train station air-conditioning cooling system

  • Ke Yang Liao
  • , Yew Khoy Chuah*
  • *此作品的通信作者
  • National Taipei University of Technology

研究成果: 期刊稿件 › 文章 › 同行評審

2 引文 斯高帕斯(Scopus)

摘要

The necessity of air-conditioning causes the enormous energy use of underground train stations. Exergy and thermoeconomic analysis is applied to the annual operation of the air-conditioning system of a large underground train station in Taiwan. The current installation and the monitored data are taken to be the base case, which is then compared to three different optimized designs. The total revenue requirement levelized cost rate and the total exergy destruction rate are used to evaluate the merits. The results show that the cost optimization objective would obtain a lower total revenue requirement levelized cost rate, but at the expense of a higher total exergy destruction rate. Optimization of thermodynamic efficiency, however, leads to a lower total exergy destruction rate, but would increase the total revenue requirement levelized cost rate significantly. It has been shown that multi-objective optimization would result in a small marginal increase in total revenue requirement levelized cost rate, but achieve a significantly lower total exergy destruction rate. Results in terms of the normalized total revenue requirement levelized cost rate and the normalized total exergy destruction rate are also presented. It has been shown by second law analysis when applied to underground train stations that lower annual energy use and lower CO2 emissions can be achieved.

原文英語
文章編號86
期刊Entropy
卷18
發行號3
DOIs
出版狀態已出版 - 01 03 2016
對外發佈是

文獻附註

Publisher Copyright:
© 2016 by the authors.

UN SDG

此研究成果有助於以下永續發展目標

  1. SDG13 氣候行動
    SDG13 氣候行動

指紋

深入研究「Exergy and thermoeconomic analysis for an underground train station air-conditioning cooling system」主題。共同形成了獨特的指紋。

引用此