Heat Transfer Performance of Microgroove Back Plate Heat Pipes with Working Fluid and Heating Power

Yanpeng Wu*, Jie Jia, Dongmin Tian, Yew Khoy Chuah

*此作品的通信作者

研究成果: 期刊稿件文章同行評審

9 引文 斯高帕斯(Scopus)

摘要

Micro heat pipes (MHP) cooling is one of the most efficient solutions to radiate heat for high heat flux electronic components in data centers. It is necessary to improve heat transfer performance of microgroove back plate heat pipes. This paper discusses about influence on thermal resistance through experiments and numerical simulation with different working fluids, filling ratio and heat power. Thermal resistance of the CO2 filled heat pipe is 14.8% lower than the acetone filled heat pipe. In the meantime, at the best filling ratio of 40%, the CO2 filled heat pipe has the optimal heat transfer behavior with the smallest thermal resistance of 0.123 K/W. The thermal resistance continues to decline but the magnitude of decreases is going to be minor. In addition, this paper illustrates methods about how to enhance heat pipe performance from working fluids, filling ratio and heat power, which provides a theoretical basis for practical applications.

原文英語
頁(從 - 到)982-991
頁數10
期刊Journal of Thermal Science
29
發行號4
DOIs
出版狀態已出版 - 01 08 2020
對外發佈

文獻附註

Publisher Copyright:
© 2020, Science Press, Institute of Engineering Thermophysics, CAS and Springer-Verlag GmbH Germany, part of Springer Nature.