The preliminary evaluation of design guidelines of stratum ventilation in a large tropical lecture hall

  • Y. H. Yau*
  • , Y. K. Chuah
  • , K. H. Chuah
  • , U. A. Rajput
  • , H. J. Liew
  • *此作品的通信作者
  • University of Malaya
  • INTI International University

研究成果: 期刊稿件 › 文章 › 同儕審查

5 引文 斯高帕斯(Scopus)

摘要

This article presents a study conducted to test the design guidelines of stratum ventilation (SV) for the conditions set in the tropics (Malaysia). Three different ventilation strategies and six different cases for SV were designed and examined by varying the layout of the return outlets and the air change per hour values. The ventilation strategy with a return outlet at the same level on opposite wall was found better than others. The simulation results of the medium-size room show that the thermal comfort is only favourable up to the centre region. Locations near the diffusers were noticed too cold and locations far away were too warm. In addition, the air flow pattern shows that the room has a high PPD due to quasi-stagnant zones that exist between the air jets from the diffusers. A similar condition does not exist in the small-size room, which was found under the acceptable range of PPD index (0%–25%). The ventilation strategy-1 (VS-1) is found with a greater energy saving with EUC 1.45 for the small room and 1.50 for the medium room compared to the other two ventilation strategies. The SV design guidelines are found adequate for the need of thermal comfort.

原文英語
頁(從 - 到)77-99
頁數23
期刊International Journal of Ventilation
卷22
發行號1
DOIs
出版品狀態已出版 - 2023

文獻附註

Publisher Copyright:
© 2023 Informa UK Limited, trading as Taylor & Francis Group.

UN SDG

此研究成果有助於以下永續發展目標

  1. SDG7 可負擔能源
    SDG7 可負擔能源

指紋

深入研究「The preliminary evaluation of design guidelines of stratum ventilation in a large tropical lecture hall」主題。共同形成了獨特的指紋。

引用此